In many industries and locations, there are strict safety regulations and standards for the operation and maintenance of generator sets. For example, in important places such as hospitals and data centers, generator sets must be able to start and operate reliably at all times as a backup power source. Through regular inspections and recording the operation status of the equipment, it can prove that the enterprise or unit has complied with the relevant safety regulations and avoid legal liability and safety risks due to violations. How to carry out daily inspection of diesel generator sets, Huaquan Power provides you with the following reference.
1. The diesel generator room is well ventilated, the lighting is sufficient, and there is no debris that hinders the operation.
2. The fuel and lubricating oil system hoses of the diesel generator set are firmly connected, there is no leakage in each pipeline, and the oil level in the diesel tank is about 2/3.
3. Each instrument and display screen are powered, the display is normal, and the heater is running normally.
4. The air filter is dry, clean and undamaged.
5. The valve of the coolant system is normal, the liquid level of the coolant tank is 2/3, the coolant water quality is qualified, and there is no leakage in the pipeline. The air intake filter is cleaned.
6. The control switch of the diesel generator set is in the automatic position (AUOT), and the outlet circuit breaker of the diesel generator is in the automatic position.
7. The battery voltage is normal, and the charger is working normally.
8. There is no alarm on the local control panel of the diesel generator set.